Potential Transformers

POTENTIAL TRANSFORMERS (1- Phase/ 3- Phase)


1) Secondary Voltage Rating – 110V or 63.5V

2) Primary Voltage Rating

3) Accuracy Class- upto 0.2 Class

All our products are type tested in CPRI /ERDA / equivalent NABL accredited test labs, as per IS:2705 and IS:3156.
Products are supplied with accessories like Terminal Connectors, Junction/ Marshaling box as per customer requirement.

Transmission Line Equipment and Accessories

NABL Scope of Testing

Test

Test Method

Year

LL

Unit

UL

Unit

Power frequency dry withstand test on primary terminals-

Common mode (separate source) withstand test - for Unearth VT

IS 3156 (Part 1)

1992

10

kV

95

KV

 

IS 16227 (Part 2)

2016

10

kV

95

KV

 

IEC 61869-3

2011

10

kV

95

KV

 

Power frequency dry withstand test on primary terminals-

Common mode (separate source) withstand test -  for Earthed VT

IS 3156 (Part 1)

1992

1

kV

5

KV

 

IS 16227 (Part 3)

2015

1

kV

5

kV

 

IEC 61869-3

2011

1

kV

5

KV

 

Power frequency dry withstand test on primary terminals-

Differential mode (Induced) AC Voltage test for Unearth/Earthed VT

IS 3156 (Part 1)

1992

1.81

kV

95

KV

 

IS 16227 (Part 3)

2015

1.81

kV

95

KV

 

IEC 61869-3

2011

1.81

kV

95

KV

 

Power frequency dry withstand test on secondary terminals

IS 3156 (Part 1)

1992

1

kV

5

kV

 

IS 16227 (Part 3)

2015

1

kV

5

kV

 

IEC 61869-3

2011

1

kV

5

KV

 

Verification of terminal marking and polarity-Visual Test

IS 3156 (Part 1)

1992

0

0

0

0

 

IS 3156 (Part 2)

1992

0

0

0

0

 

IS 3156 (Part 3)

1992

0

0

0

0

 

IS 16227 (Part 3)

2015

0

0

0

0

 

IEC 61869-3

2011

0

0

0

0

 

Determination of Voltage (Ratio) error

IS 3156 (Part 1)

1992

0

%

3

%

 

IS 3156 (Part 2)

1992

0

%

3

%

 

IS 3156 (Part 3)

1992

0

%

3

%

 

IS 16227 (Part 3)

2015

0

%

3

%

 

IEC 61869-3

2011

0

%

3

%

 

Determination of Phase  Displacement

IS 3156 (Part 1)

1992

0

Min.

120

Min.

 

IS 3156 (Part 2)

1992

0

Min.

120

Min.

 

IS 3156 (Part 3)

1992

0

Min.

120

Min.

 

IS 16227 (Part 3)

2015

0

Min.

120

Min.

 

IEC 61869-3

2011

0

Min.

120

Min.